Load tables stranded wires and busbars

Operating Data

Operating Data for collective Tracks in Cu complies DIN 43671 and Aluminum complies DIN 43670

One track per conduct, AC at 60 Hz, environmental temperature 35 °C increasing by 30 °C. Two parallel utilized collective tracks with small distance to each other cannot collectively calculated for a double current but only 1.7 times the current for one track.
Please, see also DIN 43670 and DIN 43671.

Operating Data for Cu Braid and Cu braid Bands

Starting environmental temperature at 35 °C increasing to temperature max. at 70 °C

For more details please choose a filter.
Track Width x Thickness in mm Cross Section Quadratmillimeter Operating Current in Ampere
Cu pure Cu painted Aluminum pure Aluminum painted
12 x 2 24 108 123 80 100
15 x 2 30 128 148 95 125
15 x 3 45 162 187 134 154
20 x 2 40 162 189 120 165
20 x 3 60 204 237 168 196
20 x 5 100 274 319 225 265
25 x 3 75 245 287 202 237
25 x 5 125 327 384 270 318
30 x 3 90 285 337 237 278
30 x 5 150 379 447 313 370
40 x3 120 366 435 280 355
40 x 5 200 482 573 400 474
40 x 10 400 715 850 595 705
50 x 5 250 583 697 485 577
50 x 10 500 852 1020 705 850
60 x 5 300 688 826 566 680
60 x 10 600 985 1180 820 990
80 x 5 400 885 1070 733 890
80 x 10 800 1240 1500 1030 1270
100 x 5 500 1080 1300 820 1080
100 x 10 1000 1490 1810 1270 1540
120 x 10 1200 1740 2110 1540 1870
160 x 10 1600 2220 2700 1750 2300
200 x 10 2000 2690 3290 2150 2850
For more details please choose a filter.
Cross Section in Quadratmillimeter Current in Ampere
0.1 5
0.14 6
0.2 7
0.25 9
0.35 10
0.5 12.5
0.75 15
1 18
1.5 21
2.5 30
4 40
5.25 44
For more details please choose a filter.
Cross Section in Quadratmillimeter Current in Ampere
6 55
8 70
10 85
16 120
25 150
35 195
50 250
70 300
95 360
120 420
150 480
185 570
For more details please choose a filter.
Cross Section in Quadratmillimeter Current in Ampere
240 670
300 780
400 950
500 1100
625 1300
800 1500
1000 1800
1500 2200
2000 2400
3000 3000